Temperature Controller |
Features |
Compact Size |
48mm x 48mm front panel, 110mm depth |
Universal Temperature Input |
No Jumper Setting. Select type of thermocouple or RTD from front
panel keyboard. |
Universal Output |
Select Output between relay and SSR with a single jumper setting. |
Ultra Stable Power Supply |
SMPS immune to themost irregular supply lines. |
Modular Construction |
Plug-in construction & optional output modules for Blower &
Heater Fail safety. |
Soak Timer |
0 to 9999 min. for batch processes. End of Soak output is mutually
exclusive with Blower output. |
Heater Fail Safety |
Optional for Plastics Machines- in case of heater failure controller
trips the machine supply or generates an alarm. |
Digital Communication |
Optional. RS 485 port for PV/SV & alarm transmission. Mutually
exclusive with Heater Fail Safety option. |
Plug-n-play Logic |
Completely eliminates the need for tuning of any sort. Just configure
the controller for Input type, output type and the temperature range.
The controller is now ready for operation at any sepoint on any machine/equipment |
Standard Features |
User Interface |
Display |
2 rows of 4 digit x 7 segment high intensity LED
Upper Row: Process Value in Red
Lower Row: SetValue in Green |
Key Board |
4 front panel keys for parameter settings |
|
Input |
Universal, User selectable through front panel keys
Thermocouple: J, K, R, S, T
RTD: Pt100, 3-wire, DIN 43760 |
Accuracy |
± 0.25% of reading, ± 1 LSD, ±1ºC |
Measuring Rate |
5 samples per second (sampling time 200mS) |
Output 1 |
User selectable through jumper setting
Relay: 5 A/ 230 V AC, 5A/30 V DC, resistive load
DC Pulses: 5 VDC@ 40 mA(non-isolated) for SSR |
Output 2 (Optional) |
Relay: 5 A/ 230 V AC, 5A/30 V DC, resistive load (for
Blower/ End of Soak output) |
Output 3 (Optional) |
Relay: 5 A/ 230 V AC, 5A/30 V DC, resistive load (for
Heater Fail Safety) |
Communicatin (optional)(Abridged) |
Serial, Half duplex, 2 wire RS 485, Slave mode.
Scopte restricted to PV, SV & alarm transmission only
Baudrate 9600 (fixed)
ID- settable - 1 to 31, Proprietary Protocol |
Control Mode |
Plug-n-Play PID (X-THERM Algorithm) |
Corrections |
Automatic CJC for T/C, automatic LRC for
3-wire Pt100 |
Supply Voltage |
85 to 264 V AC, 50/60 Hz |
Environmental |
Operating : 0 to 55ºC, 5-95% RH non-condensing
Storage : -10 to 70ºC, 5-95% RH non-condensing |
Panel Sealing |
Conforming to IP 65, NEMA 4 X |
Electromagnetics |
Conforming to Generic Emissions standard
EN50081-2 and general immunity requirements of EN50082-2 (95) |
Safety Standard |
Conforming toEN61010, installation category
2 (voltage transients must not exceed 2.5KV) |
Approvals |
CE, URL |
 |
|